DW-6092 3 PHASE POWER ANALYZER
Brand:A.O.I.P
SKU:DW-6092
SD card real time data recorder,
3 PHASE POWER ANALYZER
Model : DW-6092
* 3 phase/4 wire, 3 phase/3 wire, 1 phase/2 wire, 1 phase/3 wire
* True rms measurement for ACA, ACV.
* True power : W, KW, MW.
* VA, KVA, MVA, VAR, KVAR, MVAR.
* PF (power factor), phase angle.
* KWH, KVAH, KVARH, PFH.
* Voltage measurement range: 10 to 600 ACV
* Current measurement range: 0.2 A to 1200 ACA.
* Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
* Real time data recorder with SD card.
* RS232/USB computer interface.
* Display all measuring electrical wave shape.
* Patent: Taiwan, China, Japan, Germany, USA pending.
Accessories Included:
Instruction manual.......................1 PC
Test Leads (TL88-4AT)................. 1 Set (4 PCs)
Alligator clips (TL88-4AC)..............1 Set (4 PCs)
Clamp Probe ( CP-1200 ).............. 3 PCs
AC to DC 9V adapter.....................1 PC
SD card ( 2 G )............................ 1 PC
Carrying bag................................1 PC
Optional Accessories:
USB Cable , USB-01, RS232 cable, UPCB-02, Data Acquisition software, (SW-U811-WIN)
Circuit | Custom one-chip of microprocessor LSI circuit |
Display | LCD Size: 81.4 X 61 mm ( 3.2 X 2.4 inch ) , Dot Matrix LCD (320 X 240 pixels ) with back light |
Measurement | ACV, ACA, AC WATT ( True Power ),AC WATT( Apparent Power ), AC WATT( Reactive Power ), Power factor, Phase angle, Frequency |
Wire connections | 1P/2W, 1P/3W, 3P/3W, 3P/4W |
Voltage ranges | 10 ACV to 600 ACV, auto range |
Current ranges | 0.2 ACA to 1200 ACA, auto range/manual range |
Safety standard | IEC1010 CAT III 600 V |
ACV input impedance | 10 Mega ohms |
Range select | ACV (Auto range), ACA (Auto range & manual range) |
Clamp frequency response | 40 Hz to 1 KHz |
Spec. tested frequency | 45 to 65 Hz |
Over load protection | ACV (720 ACV rms), ACA (1300 ACA with clamp probe CP-1200) |
Over Indicator | Show " OL ". |
Under Indicator | Show " UR ". |
Data Hold | Freeze the display reading |
Data Record | SD Card Record |
Sampling Time | Approx. 1 second |
Power ON/OFF | Manual OFF by push button |
Real time data logger | Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/hour/mimute/second ) download to the Excel. Integration time for data logger : 2 seconds to 7200 seconds, t |
Data Output USB/RS232 * Computer interface | RS232 computer serial interface :Connect the optional USB cable USB-01 will get the USB plug. Connect the optional RS232 cable UPCB-02 will get the RS232 plug. |
Operating Temperature | 0 to 50℃ ( 0 to 122℉ ) |
Operating Humidity | Less than 80% R.H |
Power Supply | DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy duty battery), AC to DC 9V power adapter. |
Power Consumption | Meter : 300 DCmA, Clamp : 20 DCmA. |
Clamp max. conductor Size | 86 mm ( 3.4 inch ) Dia |
Weight | Meter: 1049g ( includes batteries ), Clamp : 522g |
Dimension | Meter : 225 X 125 X 64 mm( 8.86 X 4.92 X 2.52 inch ), Clamp : 210 X 64 X 33mm( 8.3 X 2.5 X 1.3 inch ), Clamp Jaw : 50 mm (2.0 inch)- outside |